Chiller Performance Starts With a Clear Measurement Boundary
A chiller transfers heat from a chilled-water circuit to another medium. In a water-cooled installation, condenser-water pumps and cooling towers also affect the performance of the cooling system.
Distinguish chiller-only electrical consumption from whole-plant consumption. An improvement at the chiller can be offset by additional pumping or fan power. Record what your calculation includes before comparing results.
Reference for system-level thinking: Trane — Chilled-Water System Design Trends.
Worked Example: Cooling Duty and Efficiency
Illustrative example: these assumed values demonstrate arithmetic, not actual plant results or recommended operating targets.
For water, a useful approximate heat balance is:
Cooling duty (kW) = mass flow (kg/s) × specific heat (kJ/kg·K) × temperature difference (K).
Assume 100 m³/h of water, density 1,000 kg/m³, specific heat 4.186 kJ/kg·K, return temperature 12°C, and supply temperature 7°C.
- Mass flow = 100 × 1,000 ÷ 3,600 = 27.78 kg/s.
- Cooling duty = 27.78 × 4.186 × 5 ≈ 581 kW.
- Cooling capacity = 581 ÷ 3.517 ≈ 165 refrigeration tons.
If the measured chiller electrical input is 110 kW:
- COP = 581 ÷ 110 ≈ 5.29.
- Chiller efficiency = 110 ÷ 165 ≈ 0.67 kW/TR.
These are illustrative values, not a pass/fail target. Use actual fluid properties for glycol mixtures, and verify flow and temperature measurements. Small sensor errors become significant when the temperature difference is small.
When Results Change
Record load, chilled-water temperatures, condenser conditions, electrical input, and control status. Compare similar operating periods before concluding that efficiency has deteriorated.
A low water-temperature difference alone does not identify a refrigerant fault. The load, water distribution, bypassing, controls, and measurement quality all deserve review. Refrigerant diagnosis and work belong to qualified personnel using the equipment procedure.
Next step: Calculate cooling duty and clearly label whether your electrical input covers the chiller or the entire plant.
Record observations only where it is safe. Inspection inside equipment, electrical testing, chemical work and changes to protective controls require qualified personnel, approved isolation and the installed equipment manual. Never bypass a trip or repeatedly restart unsafe equipment. Engineering disclaimer
Measurements To Record
- Evaporator entering and leaving water temperatures
- Condenser entering and leaving water temperatures
- Water flow and chiller electrical input
- Refrigerant pressures and alarm history
Maintenance Checklist
- Record chilled-water and condenser-water temperatures.
- Trend flow, differential pressure and kW per cooling output.
- Review refrigerant alarms and compressor start counts.
- Plan water treatment and heat-exchanger inspection.
Evidence-Based Diagnosis
Insufficient cooling
- Possible Causes
- Higher load; reduced water flow; fouling; condenser problems.
- Evidence To Collect
- Verify water temperatures and measured flow; compare loading and condenser conditions with the design baseline.
- Qualified Follow-Up
- Address confirmed water-side problems first. Use a licensed refrigeration technician for refrigerant-side assessment.
High condenser pressure
- Possible Causes
- Warm condenser water; restricted airflow on air-cooled units; fouled heat-transfer surfaces.
- Evidence To Collect
- Compare condenser conditions with ambient temperature, cooling-tower performance and previous clean-system readings.
- Qualified Follow-Up
- Arrange inspection of airflow or water circuits and cleaning. Do not bypass high-pressure protection.
Frequent cycling
- Possible Causes
- Low load; narrow control band; inadequate system water volume; sensor error.
- Evidence To Collect
- Review starts per hour, demand trend and temperature-sensor agreement.
- Qualified Follow-Up
- Have a controls specialist assess staging, system volume and permitted start intervals against the manufacturer instructions.
Record The Confirmed Result
Keep the asset model, time, load, ambient conditions, alarm code and relevant readings together. Compare with the last healthy baseline. Record the confirmed cause, approved corrective action and readings after restoration; check that the improvement persists before closing the investigation.
